What is the best practice to add custom measurement in PME?
Issue:
How to add custom measurement with metadata
Product Line:
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment:
Manual Data Editor
Cause:
The best practice to add a custom measurement before adding is by using the “Manual Data Editor”.
The main reasons are:
- Manual Data Editor adheres to naming convention rules in PME,
- Special Characters are largely restricted
- The most common predicates can be set up in the interface
- Cumulative, Unit, Aggregation
The most important aspect of this best practice is the naming convention rules and the avoidance of special characters in the name. If a user were to add a custom measurement in another manner such as custom measurement logged via a meter, logged via the VIP, setup via ETL or OPC driver they could technically add as many special characters as they like to the name. The problem is these special characters would make it impossible to edit the custom measurement and associated metadata settings later. Therefore, the best practice is to always use a sanctioned tool such as the “Manual Data Editor” to ensure the new custom measurement is set up as expected in the system.
Resolution:
Manual Data Editor is found in the Management Console (Tools tab -> System -> Manual Data Editor).
You can use Manual Data Editor to create new, custom measurements in PME. These measurements are available anywhere in the software.
To create a new measurement:
- In Manual Data Editor, click Load New Data to open the Load Data dialog box.
- In Load Data, click Create new Measurement to open the Create new Measurement dialog box.
- In Create new Measurement, enter the relevant information for the new measurement.
- Click Create to add the new measurement to the system.
- (Optional) Repeat steps 2-4 to add additional measurements.
- Close Manual Data Editor.
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.