Importing Control Expert Classic project returns error 'The IO Scanning mode must be set to enhanced'
This occurred because the 'Control Expert Classic project' was not built using Control Expert 15.1 Classic with the I/O Scanning Mode set to Enhanced before creating the export file (.zef). This is required because:
- The I/O scanning mode cannot be changed after import.
- The Topology Manager only supports Enhanced mode.
Use the following steps to set the IO Scanning mode to enhanced:
- Open the project with Control Expert Classic 15.1.
- Open the project settings.
- Click on Build Settings.
- Click on IO Scanning mode.
- Select Enhanced from the drop down menu.
- Click on Apply.
- Save the changes.
- Export the project as a '.zef'.
Publikováno pro: Schneider Electric Česká republika


Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.