How can you setup the ATV320 Drive over Ethernet IP using assemblies 20 and 70?

Issue:

ATV320 using assemblies 20 and 70 with Ethernet IP

 

Product Line:

ATV320 with Ethernet TCP/IP option card part number VW3A3616.

 

Environment:

All

 

Cause:

Setting up Ethernet IP using assemblies 20 and 70.

 

Resolution:

 

Suggest you use Somove and ATV320 DTM file to configure the ATV320 drive

https://www.se.com/us/en/product-range/2714-somove/#software-and-firmware

 

PLC example setup:

Build a Generic Ethernet module configuration on the PLC side. Choose assemblies 20 and 70 for 2 words each.

20: Basic speed control output, size 2 words / 8 bytes

70: Basic speed control input, size 2 words / 8 bytes

 

The EtherNet/IP card translates the commands, behavior and monitoring information from of ODVA profile (on

the network) to the CiA402 profile (in the drive).

 

phot 1

phot 2

 

Phot 3

 

 

Setting up and programming the drive using Somove Software Example only.

Setting up the IP, subnet and gateway address

 

phot 4

 

 

Programming the drive per case II example in the Programming manual

 

phot 5

 

 

 

 

 

Commanding the drive to start, reset fault and speed control

1st word in the output table is the command word bit 0 =1 is run and bit 2 is fault reset

2nd word in the output table is the speed ref in rpms.

 

Reading Status from the drive like running, fault and motor speed.

1st word in the input table is the ETA Status word bit 0= fault and bit 2= Drive running

2nd word in the input table is the motor speed in rpms

 

 

 

 

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.