Can the ATV212 be used at high elevation?
Issue:
Customer wants to use the ATV212 at elevation over the maximum elevation listed in the Manual (1000 meters).
Product Line:
Altivar 212
Environment:
Altitude over 1000 meters
Cause:
High elevation jobsite
Resolution:
The ATV212 products is limited at 1000m without derating.
You can reach 3000m with current derating 1 % per 100m.
The limit is 2000m for Corner grounded system.
We can not be higher because the rated insulation of the product is designed for altitude up to 3000m.