Jak vám dnes můžeme pomoci?

How to connect my Control Expert client to the server ?

Before starting Control Expert Topology Manager (TM) on the client side, please follow these steps:

  1. Close TM on the server side.
  2. Open the Server Configuration.
  3. In the Listening Connections tab, update the Listening IP address:
    • Either select the Ethernet card used to communicate with the client PC,
    • Or enter 0.0.0.0 to listen on all Ethernet interfaces.

Server Configuration listenning IP address

4- Apply the changes and close the configuration tool.
5- On the client side, open TM and go to User Preferences.
6- In the Networks and Servers tab, update the Control Expert Server Address with the correct IP and port:
  • For example: IP = 192.168.189.1, Port = 19950.

User Preferences define IP address of TM server

7- Close and relaunch TM on the client side.

You should now be able to connect to the server successfully.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie