Jak vám dnes můžeme pomoci?

NetBotz graphs plot only 2 data points

Issue:
NetBotz graphs have only 2 data points

Product Line:
NetBotz

Environment:
NBWL0755
NBRK0750

Cause:
NetBotz sensors that do not change will only show 2 data points in a graph. For instance, a door sensor that has not opened will have a closed State at the beginning of the graph and at the end. No other points will be recorded. The same will be seen for a temperature sensor if the temperature has not changed.

Conversely, if there have been multiple changes, you should see multiple points on the graph.

Resolution:
Upon checking Sensor data history excel, it shows all sensor data captured during this time period.

This function works as designed.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie