How do I upgrade the firmware of the BMENUA0100 OPCUA server module?

First log into the module via the web pages and go to the cyber security setup tab then select access control

image1

Create an account and select the appropriate roles for the user, "installer" necessary

image2

Apply the changes

image3

Launch the Automation Device Maintenance utility and select settings then package settings. The package location is where you copy the firmware file to

image5

The firmware should be available in the list under the data package

image6

Next, select Device/Loading tab and select Add

image7

Set the connection to HTTP/HTTPS and enter the IP address of the BMENUA0100 module then select ok

image8

Device should appear in the device list, make sure the data package reflect the firmware version you are upgrading to. Then select "Device Login" icon and enter the user credential of the module and select "connect"

image8b

The device login icon should turn green indicating a valid login. Next select the "Update Firmware" button at the bottom

image9

Schneider Electric Česká republika

Zjistěte více
Produkt:
Zjistěte více
Produkt:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie