Jak vám dnes můžeme pomoci?

Using Pick Action For "Change Main Server" Action

This Pick Action can be used to switch between servers for users in ViewX with restricted  database access. Administrators may need a simple and secure way to switch between servers—especially during or after a failover event. The Pick Action feature provides a streamlined solution for this scenario. With a single button click, the Pick Action presents a list of available servers. Users can then select the desired server from the list, enabling quick and controlled server switching without requiring elevated database permissions

  • Create a new mimic and create a button from the Graphical tab in ViewX.
  • Double click the button to display “Button Properties” dialog.

Change_Main_Server

  • Click the “Pick Action” button.
Pick Action
  • From the Pick action configuration, select “Method” and click “Next”

Method

  • Click the ellipsis on the right and locate root explorer.
  • Beside “Method” select from the drop-down list “Change Main Server” and click “Next”.
  • Click “Next” button twice and “Finish”.
  • Save changes and place in “Run Mode”.

Pick Action Configuration

Schneider Electric Česká republika

Zjistěte více
Produkt:
Zjistěte více
Produkt:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie