PowerChute cannot register with Network Management Card/s and report a security certificate rejection.

Article available in these languages:

  • Španělština

Issue:
PowerChute cannot register with all Network Management Cards due to the rejection of the security certificate.

Product:
PowerChute Network Shutdown v5

Environment:
All support OS

Cause:
The Common Name (CN) values on the Network Management Cards SSL certificate CN value may be set to “.” (Period) by default on new NMCs.

To view the Network Management Card (NMC) security information, log into the Network Management Card and go to Configuration > Network > Web > SSL Certificate > Validate certificate.
SSL Certificate

Solution:
Use the Network Management Card Security Wizard to create and upload a new SSL certificate or generate a new self-signed certificate on the Network Management Card. In the Network Management Card UI, navigate to Configuration > Network > Web > SSL Certificate and select the option to remove the existing certificate. This will reboot the NMC and generate a new self-signed certificate with the CN value updated to use the Network Management Cards IP address or hostname.
remove SSL certificate

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie