What would cause the ATV680 AFE drives to show incorrect line voltage measurements on the HMI?

Issue:

ATV680 AFE drives is showing incorrect line voltage measurements on the HMI?

Product Line:

ATV680 and ATV980 enclosed drives.

Environment:

All

Cause:

Loose wiring connection, blown fuse etc.

Resolution:

If the input Line voltage is measuring the correct line voltage phase to phase and to ground.

Remove power and check the following:

-Check the main power fuses they have a tab that will popout to show if they are blown.

-Check the L1 L2 L3 input fuses on the RFI filter circuit board (bottom right corner of ATV680 enclosure if you're facing the drive)

-Check for loose wires on the L1 L2 L3 terminals of the RFI filter circuit board.

-Hire field services to come out and check or replace the RFI circuit board or the Power board.

Example of incorrect input or line voltage readings on the HMI> Drive is running and or in IDLE mode.

Main menu

Display menu

Drives Parameters

Mains voltage 338vac

L1= 239vac is incorrect (480vac is correct reading)

L2= 239vac is incorrect (480vac is correct reading)

L3= 480vac is the correct reading

DC bus= 680vdc (Running)

DC bus= <20vdc (IDLE mode)

In this example the L2 wire was disconnected on the RFI filter board.

A RFII fitler picturesHMI showing voltages example A

Schneider Electric Česká republika

  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie