Why Does ViewX Fail to Connect to the Server with the Error "ClearSCADA.Client.SecureSessionRequiredException"?

Issue:

In some cases, a ViewX client may fail to connect to a Geo SCADA server and display the following error message: "Exception of type 'ClearSCADA.Client.SecureSessionRequiredException' was thrown."

This issue can occur when the SecureConnection setting stored in the SYSTEMS.XML file does not match the security requirements of the server. If the client is configured to use a non-secure connection while the server requires a secure session, ViewX will be unable to establish communication and the connection attempt will fail with the error above.



ViewX error

Resolution:

To resolve the issue, verify the SecureConnection setting in the SYSTEMS.XML file located in: C:\ProgramData\Schneider Electric\ClearSCADA



XML file location



Ensure that the value is set to: SecureConnection="true"



Change secure connection tab to true

If the value is set to false, close ViewX, update the setting to true, save the file, and restart the client before attempting to reconnect.

Schneider Electric Česká republika

Zjistěte více
Produkt:
Zjistěte více
Produkt:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie