Micrologic Devices Not Logging in PME
Issue
Micrologic devices are no longer logging measurements or logging them very infrequently.
Product Line
Power Monitoring Expert 2022
Environment
Translators
Cause
In PME2022 additional logging was enabled for the following load profile registers:
- Load Profile 0 to 49%, Load Profile 50 to 79%, Load Profile 80 to 89%, Load Profile 90 to 100%, and Rate Of Wear Counter.
Unfortunately, the xml file required an update to exclude those registers from scattered reads.
Resolution
- Navigate to the .\Schneider Electric\Power Monitoring Expert\system\translator folder on your server
- Locate the micrologic_p.xml and micrologic_p.ion files
- Copy/Paste these files to the .\Schneider Electric\Power Monitoring Expert\config\translator folder
- Open and edit the micrologic_p.xml file with a text editor (Notepad, Notepad++, etc)
- add the following text at the very bottom of the file (just above </ModbusMap>):
<TransactionConfiguration>
<DatasetAddressBlock ModbusAddress="429880" NumberOfRegisters="8"/>
<DatasetAddressBlock ModbusAddress="429853" NumberOfRegisters="1"/>
</TransactionConfiguration>
Once completed, the last lines of the .xml file should match the screenshot below:
- Save the file
- Open the “Services” application in Windows and restart the ION Network Router Service and ION Site Service.
Repeat Steps 1 through 6 for the A, E, and H version driver files
- micrologic_a.ion
- micrologic_a.xml
- micrologic_e.ion
- micrologic_e.xml
- micrologic_h.ion
- micrologic_h.xml
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.