Why is the boot up time longer on the ATS480, than the ATS48?

Issue:

Customer has a ATS480 and when it is powered up it shows “Welcome to Schneider” boot up screen. They state it takes about 8 seconds for the Soft start to boot up and

it’s unacceptable for their process. Any way to reduce the start-up process?

Product Line:

ATS480

Resolution:

The ATS480 have a software and hardware control that is different compared to ATS48.

After a power on of Control voltage (CL1-CL2), the starter needs about 6.5 secs for the wake up.

The reason the boot time is higher on ATS480:

The flash memory is larger and there is a increase in the time of the initialization of the file system.

ATS480 embeds a secure boot and the firmware integrity check time is significant.

Unfortunately, there is not a way to reduce this time.

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)“

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie