What does 'Demand State' mean in an M580 safety application?
The demand state refers to the condition when a safety function must act to bring a process to a safe state such as when a hazardous event or fault occurs.
In this state, the process moves from normal operation (no demand) to performing its safety action, such as de-energizing outputs, shutting down motion, or cutting power (demand).
The demand state can be either energized or de-energized, depending on how the process is designed to reach its safe condition:
-
De-energize to trip: The system becomes safe when power is removed (e.g., closing a filling valve to prevent tank overflow or stopping gas injection during a leak).
-
Energize to trip: The system requires energy to achieve safety (e.g., energizing a valve to release fire suppression water).
While the PLC safe state is always de-energized, the process demand state may differ. Ideally, both should align, but this isn’t always possible depending on the application design.