Jak vám dnes můžeme pomoci?

Every time I go online with the PLC using Machine Expert using the Classic Mode view, it prompts me to re-download the project. How do I fix this?

When Classic Mode is activated, a further setting will be available which is about the communication settings. The communication settings will be part of the project per default as the box is unchecked. If you have downloaded the saved and up-to-date project any new network scan will modify the project-file as the settings will be stored even they are unchanged. The project is marked (* behind project name in header) as changed and a download will be necessary.

Check the "Don't store communication settings in the project" box to be able to go directly online in classic mode - the checked box prevents project changes after a network scan.

checkbox

Schneider Electric Česká republika

  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie