Jak vám dnes můžeme pomoci?

Ecostruxure Process Expert [2023]: How to rectify the initialization issue of topology manager

This knowledge base explains the user about the issue they face when they try to launch the topology explorer.

User has migrated the system backup from EPE2020R2 to EPE2023.After they restore the system in EPE2023,they are facing the below issue when they launch the topology explorer.

Topo

It was noted that the EPE server on the customer's machine was configured to run as a service. Upon initiating the system backup migration, the Migration seems to be successful, however the topology keeps initializing continuously. There will be no errors in the logs or system server console.

Upon investigation, it was identified that when the topology manager migration started, the expected launch of the topology manager client failed. This failure prevented the creation of the TM database and resulted in the failure of loading TM in EcoStruxure Process Expert.

After changing the server setting to manual, the user executed a system backup restore leading to the successful launch of the topology manager client and the creation of the TM database.

Therefore, kindly keep the system service in manual mode while performing the migration activity and after completion of migration, user can revert back to Service mode. This is applicable for Ecostruxure process expert 2023 version.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie