Jak vám dnes můžeme pomoci?

PowerChute fails to connect with Microsoft smtp-outlook.com and smtp.office365.com to send email notifications.

Issue:

PowerChute fails to connect with Microsoft smtp-outlook.com and smtp.office365.com to send email notifications.

Products:

PowerChute Serial Shutdown v. 1.0, 1.1, 1.2, 1.3

PowerChute Business Edition 9.5, 10.x

Environment:

PowerChute is configured to use a Microsoft SMTP server as the mail server.

Cause:

As of 16 September 2024, Microsoft no longer allows username and password authentication to connect to its SMTP servers. PowerChute used the Microsoft user's username and password to authenticate with Microsoft SMTP servers, so it can no longer connect to send email notifications.

See:

https://techcommunity.microsoft.com/t5/outlook-blog/keeping-our-outlook-personal-email-users-safe-reinforcing-our/ba-p/4164184

Solution:

See Schneider Electric FAQ000274757

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie