Jak vám dnes můžeme pomoci?

PME2024 TGML Component Binding

Issue Description:
TGML component binding is not working in PME2024.

Environment:
PME Graphic Designer

Cause:
The binding property was changed in PME 2024, which prevents the use of component binding.

Component Binding

Below error will appear in the web application:

Web App Error

Resolution:
Follow these steps to fix the component binding issue:

  1. Navigate to the PME installation folder.
  2. Open app.js from this location: Applications\\SystemDataService\\Content\\Applications\\Diagrams\\Scripts\\TGMLviewer.
  3. Search for bindings[bindFullName] = bindName; in app.js.
  4. Comment out bindings[bindFullName] = bindName;. Workaround
  5. Save app.js.
  6. Perform an IIS reset and refresh the PME web application.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie