How to display DNP3 and/or Modbus protocol addresses in Logic Editor?
If you added DNP3 point numbers and/or Modbus register addresses before selecting the Object Protocol Address(es) in the Logic Editor custom field, you can display those addresses in the SCADAPack x70 Logic Editor:
- Go offline in RemoteConnect.
- Under My Network, right-click on SCADAPack x70 Controller Settings-DeviceDTM and select Additional Functions>Project Settings.
-
Select the Object Protocol Address(es) in Logic Editor Custom Field checkbox.
- Click Ok.
- A window will pop up " The Project Settings have been updated. Click the View log File button to see the complete list of changes". and select Close button.
- Open Logic Editor
- Under Project > Variables & FB Instances, double click on Derived Variables and view Custom field.
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.