PME 2024- Tamper detected error. A valid software license could not be found.

Product Line
Power Monitoring Expert 2024
_____________________________________________________________
Environment
License Configuration Tool
_____________________________________________________________
Issue :
A valid software license could not be found.
A valid license could not be found

The system logs are flooded with the error: Tamper detected: FlxDotNetClient.SvcSessionException: MID=0, SID=0, EID=6

_____________________________________________________________
Proposed Solution

Solution 1:

Import the attached 3 certificates to the Trusted Root Certification Authority through the Manage Computer Certificates interface.

  1. VeriSign Universal Root Certification Authority.cer
  2. VeriSign Class 3 Public Primary Certification Authority - G5.cer

DigiCert Trusted Root G4.cer

Trusted Root Certification

Then run the below PowerShell script after getting the exported certificate in the system.

Change the path of the exported file in the following script and run it in PowerShell ISE in administrator mode.

$sst = ( Get-ChildItem -Path C:\certs\roots.sst )

$sst| Import-Certificate -CertStoreLocation Cert:\LocalMachine\Root

Solution 2:
If the previous solution fails, rebuild the certificate chain using a functioning PME system.

From this working PME system, export the three specified certificates. You can find the link below to export the trusted root certificate from the functioning machine.
http://woshub.com/updating-trusted-root-certificates-in-windows-10/

Then run the below PowerShell script in the non-working system after getting the exported certificate in the system:

Change the path of the exported file in the following script and run it in PowerShell ISE in administrator mode

$sst = ( Get-ChildItem -Path C:\certs\roots.sst )

$sst| Import-Certificate -CertStoreLocation Cert:\LocalMachine\Root

Schneider Electric Česká republika

Přílohy
VeriSign Universal Root Certification Authority.cer [1.18 KB]
VeriSign Class 3 Public Primary Certification Authority - G5.cer [1.21 KB]
DigiCert Trusted Root G4.cer [1.39 KB]
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie