Report - Multi Device Usage Report - An error occurred while making initial report viewer settings
Issue:
When Generating the Multi-Device Usage Report for a 1-year period in PME 2023, the following error message appears "An error occurred while making initial report viewer settings"
Product Line:
PME 2023
Cause:
A timeout error occurs a few minutes after initiating the report generation.
please refer the attached image for reference.
Resolution:
Database Warning: “This article contains information about editing the database. Please note, editing or updating anything in DB may cause permanent damage and result in PME to function improperly. This procedure should only be performed by users familiar with SQL Server Management Studio. Kindly take a backup of the database before performing any such action."
To resolve the issue, perform the following steps:
- Update Report Timeout to 600 seconds in the Management Console.
- Open SQL Server Management Studio(SSMS), navigate to the ION_Network database, and locate dbo.vCFG_ConfigItems table. Modify the following settings:
- BatchReportRenderTimeout = 3600 seconds
- MaxNumberofRecords = 1200000
- WebService Proxy Timeout = 930 seconds
- Perform the following steps:
- Run iisreset in command prompt with administrator mode
- Restart IONAppMod Services
- Clear browser cache
Please refer to the attached image for configuration details and reference.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.