IRIG‑B Synchronization (Arbiter protocol) — Interbyte Time Adjustment on SAGE RTU
Issue:
IRIG‑B time synchronization from an Arbiter source is intermittent or fails; the SAGE Arbiter task reports receive errors and time events are not being applied reliably.
Product:
SAGE RTU (Arbiter IRIG‑B protocol)
Environment:
SAGE RTU GUI using Arbiter IRIG‑B for time sync
Cause:
The Interbyte Timer in the Arbiter protocol configuration is expiring before the second byte of each transmission arrives. In a captured session, the 2nd byte was received ~100 ms after the 1st byte (Protolyzer highlighted in purple as a timing violation), while the SAGE Interbyte Time was set to the default 50 ms. When this timer expires, the Arbiter task interprets it as a reception error and may discard the message, disrupting synchronization.
Resolution:
- Increase the Interbyte Time in the SAGE Arbiter protocol configuration from the default 50 ms to 150 ms.
- Apply/Save the protocol changes and restart the Arbiter task (or the RTU communication service, if required by your configuration).
- Retest with a Data Trap on the same port and review in Protolyzer:
- Confirm that the 2nd byte timing no longer violates the Interbyte parameter (no purple timing flags).
- Verify that the Arbiter task logs no further receive‑timeout or frame errors.
- Monitor synchronization: check that time events are now accepted and that the RTU clock remains aligned.
- If needed, fine‑tune the Interbyte Time upward in small increments to accommodate line latency or source behavior; avoid setting it excessively high to prevent unintended message grouping.
Notes / Tips:
- If issues persist, also review baud rate, parity, and stop bits on both Arbiter and SAGE ends, cable integrity, and grounding/noise conditions.
- Keep a short capture pre‑ and post‑change to document improvement for your records.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.