Sage RTU DNP3 Secure Authentication version (DNP SA) Compatibility
Issue:
Customer requests confirmation whether the Sage RTU products supports DNP3 Secure Authentication (DNP SA), along with guidance on upgrade paths and options to meet security requirements.
Product:
SAGE 2400
SAGE 3030M
SAGE 4400
SAGE 14x0
Environment:
- Multiple substations standardized on Sage RTUs with standard DNP3 (non-SA)
- Organizations-wide push to adopt more secure DNP3.
- Installed base includes hardwired I/O connected via expansion cards.
Cause:
- The Sage RTU’s DNP3 implementation supports only up to a specific Secure Authentication Version.
- No further firmware developments about DNP SA will be released.
- Achieving DNP3 SAv5 or higher would require newer hardware.
Resolution:
- Current Capability: The Sage RTUs supports DNP3 SAv2 only; it does not support SAv5/SAv6.
- Roadmap / Firmware: There is no indication for a new firmware releases enabling SAv5+ on Sage RTUs.
- Recommended Path: To attain DNP3 SAv5 or newer, plan to transition to Powerlogic T500 hardware.
- Gateway Options: If an interim solution is needed, explore secure gateway approaches; however, validation and compatibility with Sage environments should be confirmed case-by-case.
Next Steps:
-
- Engage Marketing/Offer Management for roadmap, timelines, validated gateway options, and migration guidance.
- Point of contact: T500 Offer Manager for US/Canada/Mexico (for accurate, current information).
- Assess I/O Migration: For sites with hardwired I/O expansion cards, ensure the proposed solution includes a migration or retention plan (e.g., compatible I/O modules, remote I/O, or structured cutover strategy).
- Plan Phased Upgrade: Prioritize high-risk substations, conduct a pilot with Powerlogic T500, and verify DNP3 SA configuration, interoperability with the SCADA/EMS, and commissioning procedures.
- Document Cybersecurity Posture: Update site standards and commissioning checklists to reflect SA keys management, authentication policies, and fallback behavior.
- Engage Marketing/Offer Management for roadmap, timelines, validated gateway options, and migration guidance.
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.