Digital Input Mapping in GUI for SAGE RTU 2400 with Additional C3232 Input Boards
Issue:
Customer wants to understand how digital input (DI) points are mapped in the GUI when a SAGE 2400 RTU uses onboard inputs and additional C3232 DI boards connected via the J1 expansion bus.
Product:
SAGE 2400 RTU
C3232 Digital Input Expansion Board
Environment:
- SAGE 2400 RTU with onboard DI points
- Additional DI points provided by C3232 boards connected to the J1 bus
- GUI configuration for mapping DI points
Cause:
The mapping of DI points in the GUI follows a sequential hardware-based numbering system, which can be unclear when multiple DI expansion boards are added.
Resolution:
- Mapping Rules:
- Baseboard DI points: 1–16
- First DI XT card on DI expansion bus: 17–48 (32 points)
- Next DI XT card: 49–80 (32 points)
- Additional cards continue in increments of 32 points.
- Important Note:
- All DI points correspond directly to their hardware number unless some DI points are configured as counters.
- If DI points are used as counters, subtract those from the number of STS (status points).
- Keep track of DI points configured as counters to avoid misalignment in mapping.
By following these rules, the GUI will correctly reflect the hardware configuration for onboard and expansion DI points.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.