Jak vám dnes můžeme pomoci?

EAE24.1 : Windows SoftDPac is not getting started for Windows11 Operating systems in Regional languages

This knowledge base article explains how to resolve the issue which is, Windows SoftDPAC service is not getting started for Windows11 Operating systems in Regional languages like Japan, Korea etc.

The symptoms of this issue is like, when user starts Windows SoftDPAC in Ecostruxure Automation Expert, the below shown error will appear.

softdpac

This issue is happening due to change of the Ethernet Adaptor's name from English to Regional language due to the latest update in Windows11.

The workaround for this issue is to Rename the Ethernet Adaptor's from local language to English. After that, Windows SoftDPAC Service should start without any issue.

ETH

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie