How to diagnose line break for BMXART0814/0414 at mV ranges ?

Issue

How to diagnose line break for BMXART0814/0414 at mV ranges ?

Product Line

X80

Environment

Control Expert

Resolution

BMXART0814/0414 modules have the interface to enable/disable the broken wire detection function for thermocouple or thermoprobe signals as below .

TC

User is able to monitor the broken wire through channel and module Error lights at mv range.  Module variables listed below could be used to indicate wire broken status in PLC application .

I/O data type : Device DDT

When the channel selected to +/- mV , CH_HEALTH in Device DDT will report error in case of broken wire.

DDT

I/O data type : Topological

Variables CH_ERROR, CH_FLT, SENSOR_FLT in IODDT could indicate the broken wire error and function block READ_STS could be implemented to read above exact channel status.

IODDT

Schneider Electric Česká republika

Zjistěte více
Produkt:
Řada:
Zjistěte více
Produkt:
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie