Jak vám dnes můžeme pomoci?

PowerChute Network Shutdown REST API

Issue:

  1. Want PowerChute Network Shutdown to trigger OS shutdown using a remote command.
  2. Want to test the PowerChute configuration to verify the OS shuts down correctly.

Product:

PowerChute Network Shutdown

Environment:

All supported Operating Systems

Cause:

Informational

Solution:

PowerChute Network Shutdown offers a REST API. The REST API is used to command the operating system to shut down without requiring APC UPS intervention.

On a Windows system, open a command prompt as an administrator, or on a Linux system, open a terminal window as root and enter the command:

curl --user PowerChute Username:PowerChute Password -k -X POST "https://PowerChute System Hostname or IP address:6547/REST/remoteShutdown?source=test&reason=shutdownTest&active=true"

Replace PowerChute username:PowerChute Password with the username and password assigned when PowerChute was installed. Also, replace the PowerChute System Hostname or IP address with the host's FQDN or system IP address.

Example: curl --user PCNStester:Schneider1234! -k -X POST "https://192.168.0.100:6547/REST/remoteShutdown?source=test&reason=shutdownTest&active=true"

NOTE 1: Starting with Windows 10 version 1803 or later, curl.exe is included. You may need to install curl on your Linux system.

NOTE 2: Running the API will simulate how PowerChute responds during a power event that requires an operating system shutdown. When executed, the API will initiate the OS shutdown.

NOTE 3: If PowerChute is configured to send a shutdown signal to the UPS or outlet group, the command will be sent, causing the UPS or outlet group to power off after the set delay.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie