Are power cords included with APC Rack Automatic Transfer Switch (ATS) units?
Issue:
Clarification needed on whether APC Rack Automatic Transfer Switch (ATS) units ship with power cords and what type of power cords are required if not included.
Product Line:
Rack Automatic Transfer Switch (ATS) Models with detachable input power cords.
- AP4421A
- AP4423A
- AP4433A
- AP4434A
Environment:
Installation and setup of APC Rack ATS units in IT and data center environments.
Cause:
Certain APC Rack ATS models are designed to use detachable input power cords, which are not supplied with the unit. Users must select and provide appropriately rated cords based on regional certification and electrical requirements.
Resolution:
For APC Rack ATS models that support detachable input power cords, power cords are not included in the product packaging. Customers must supply their own properly rated and certified cords.
AP4421A
IEC‑rated, VDE/HAR certified
Rated: 300 VAC, 3 × 1.0 mm² minimum
Must use approved plug and outlet
Intended for listed information technology equipment
AP4423A
IEC‑rated, VDE/HAR certified
Rated: 300 VAC, 3 × 1.5 mm² minimum
Must use approved plug and outlet
AP4433A
UL Listed / CSA certified
Rated: 300 VAC, 14 AWG minimum
Must use approved plug and outlet
AP4434A
UL Listed / CSA certified
Rated: 300 VAC, 12 AWG minimum
Must use approved plug and outlet
Power Cord Length Requirements:
Minimum: 1.5 m
Maximum: 4.5 m
Exceptions apply for special installations (e.g., equipment mounted close to the receptacle)
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.