VMs are not available in the PowerChute priority list.

Issue:

VMware VMs are not shown in the PowerChute priority list.

Product:

PowerChute Network shutdown

Environment:

VMware vCenter Server

Cause:

The VMs have been added to a VMware resource pool.

In the example below, VM AlmaLinux9A and Azure23HCI have been added to resource pool 1

vCenter Server list of VMs

When viewing VMs in the PowerChute priority list, the AlmaLinux9A and Azure23HCI are not displayed.

PowerChute UI not showing the resource pool VMs

NOTE: VMs added to a resource pool will be powered off along with unprioritized VMs.

Solution:

To prioritize VMs that have been added to a resource pool, create a vApp or vApps within the resource pool and add the VMs to the vApp(s)

In the example below, we have created a Test vApp within the resource pool and added the two VMs to that vApp. The vApp has been added to a high-priority group in PowerChute so the VMs will be shutdown last and started first.

PowerChute showing the vApp that was added to the resource pool

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie