Video: Replacing the Intelligence Module in Smart‑UPS Modular Ultra 5–20 kW
Issue:
The UPS reports an intelligence module fault, communication issue or requires replacement of the intelligence module as part of troubleshooting or maintenance.
Product Line:
APC Smart‑UPS Modular Ultra 5 kW, 10 kW, 15 kW, and 20 kW
Environment:
UPS Models that begin with SRYL5K up to SRYL20K
All Serial Numbers
Cause:
The intelligence module may need replacement due to hardware failure, communication errors, or as part of service maintenance.
Resolution:
The Smart‑UPS Modular Ultra uses user-replaceable Intelligence Module part number: SRYLIM.
It is hot‑swappable when replaced one at a time without shutting down the UPS.
NOTE: Do not remove both Intelligence Modules from the UPS frame at the same time. The UPS will drop the connected load.
Intelligence Module Replacement Steps:
- Remove the front bezel located beside the display.
- Loosen the thumb screw, then slide it to the left to release the module.
- Pull the intelligence module out of the UPS.
- Slide the replacement intelligence module fully into the slot.
- Tighten the thumb screw to secure the new module.
- Reinstall the front bezel.
For a visual guide, please refer to the replacement video below.
If you have any questions or need further assistance, please get in touch with our customer care center at https://www.se.com/us/en/work/support/.
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.