How to configure automatic login at Windows Startup on a HMIG5U22?

Issue:

How can we configure an automatic logon at Windows startup on a HMIG5U22?


Product Line:

All Windows based HMIs.


Resolution:

Before applying the below procedure, it is required to disable the EWF or UWF filter (depending on Windows version) for the changes to be saved.

Once terminated, do re-enable the UWF filter.


Setting Up Auto Login


Using Netplwiz (Advanced User Accounts)

  1. Press the Windows Key + R to open the Run dialog.
  2. Type netplwiz and press Enter.
  3. In the User Accounts window, select the account you want to log in with automatically.
  4. Uncheck the box that says "Users must enter a username and password to use this computer."
  5. Click Apply.
  6. A prompt will pop up asking for your account username and password.
  7. Type your password, confirm it, and click OK


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric Česká republika

Zjistěte více
Produkt:
Zjistěte více
Produkt:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie