Jak vám dnes můžeme pomoci?
PowerChute is flagged a vulnerable to CVE-2026-49844
Issue:
PowerChute is flagged a vulnerable to CVE-2026-49844
Product:
PowerChute Serial Shutdown 1.5, 1.6
PowerChute Network Shutdown 5.2
Environment:
All supported operating systems.
Cause:
PowerChute Serial Shutdown 1.5 and 1.6 ship with Log4j versions less than version 2.25.5
PowerChute Network Shutdown 5.2 ships with Log4j versions less than version 2.25.5
Solution:
For PowerChute Serial Shutdown 1.5, 1.6 on Windows:
- Download the attached file PCSS_Log4j_Update.zip file
- Uncompress the file PCSS_Log4j_Update.zip
- Open a command prompt as an administrator
- Change directory to the PCSS_Log4j_Update.zip directory that was created when the zip file PCSS_Log4j_Update.zip was uncompressed.
- Run the command run_patch.cmd
The patch will remove the current log4j files and replace them with log4j version 2.26.1.
For PowerChute Network Shutdown 5.2 on Windows:
- Download the attached file PCNS5.2_log4j_update.zip file
- Uncompress the file PCNS5.2_log4j_update.zip
- Open a command prompt as an administrator
- Change directory to the PCSS5.2_log4j_update directory that was created when the zip file PCSS5.2_log4j_update.zip was uncompressed.
- Run the command run_patch.cmd
The patch will remove the current log4j files and replace them with log4j version 2.26.1.
For PowerChute Network Shutdown version 5.2 on Linux
- Download the attached log4j-2.26.1.tar file, and if needed, copy the file to the Linux system.
- Uncompress the log4j-2.26.1.tar file. The command is tar -xvf log4j-2.26.1.tar.
- Stop the PowerChute service. The command is systemctl stop PowerChute
- Change directory to the PowerChute lib directory. The default path is /opt/APC/PowerChute/group1/lib
- Move the log4j2 files to the APC directory. If PowerChute resides in the default path, the command is mv /opt/APC/PowerChute/group1/lib/log4j2* /opt/APC
- Change directory to the log4j-2.26.1 directory that was created when you uncompressed the tar file.
- Copy the log4j-api-2.26.1jar, log4j-core-2.26.1.jar, log4j-slf4j-impl-2.26.1.jar to the PowerChute lib directory that resides where PowerChute resides. If PowerChute resides in the default path, the command is cp log4j2* /opt/APC/PowerChute/group1/lib
- Start the PowerChute service. The command is systemctl start PowerChute
For PowerChute Serial Shutdown versions 1.5 and 1.6 on Linux
- Download the attached log4j-2.26.1.tar file, and if needed, copy the file to the Linux system.
- Uncompress the file. The command is tar -xvf log4j-2.26.1.tar.
- Stop the PowerChute service. The command is systemctl stop PBEAgent
- Change directory to where PowerChute has been installed. The default path is /opt/APC/PowerChuteSerialShutdown/Agent/
- Move the current log4j files. If PowerChute was installed to the default path, the command is mv /opt/APC/PowerChuteSerialShutdown/Agent/lib/log4j* /opt/APC
- Change directory to the log4j-2.26.1 directory that was created when log4-2.26.1.tar was uncompressed.
- Copy the new logj4 files to the PowerChute lib directory. If PowerChute was installed to the default path, the command is cp log4j.* /opt/APC/PowerChuteSerialShutdown/Agent/lib
- Restart the PowerChute service. The command is systemctl start PBEAgent
Publikováno pro: Schneider Electric Česká republika
Přílohy
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.