Machine Expert V2.3/2.5 - Password Expiration: Default Setting and Configuration

Issue / Symptoms:

Communications using login/password no longer works.

For example, HMI may be disconnected from the machine.

Same for OPC UA, FTP, Web Visu, Web Server connections.

When connecting from Machine Expert, a popup window is displayed saying that the PLC password has expired and requiring setting a new password.

This issue is due to the Password Expiration setting that was introduced in Machine Expert V2.3 and V2.5.

There is no way to determine the default expiration period when the setting remains unchanged from its default value.

Product lines:

M241, M251 and M262 controllers programmed with Machine Expert V2.3 or V2.5.

Resolution:

To confirm the default value for the Password Expiration Timeout Days that is configured in a specific Machine Expert controller, it is required to connect to the specific controller for which this value has not been changed.

For the M241, M251 and M262 controllers, the default value is 365 days. It is possible to change it from 0 to 1000 days.

There are different possibilities to prevent the expiry of the password from accessing the controller:

  • From Machine Expert
  • Via FTP connection
  • By using an SD card

See attached documents.

Note:

In case the password is already expired, only a connection from Machine Expert allows renewing it.

Nevertheless, a solution by using the Clone feature via SD card can be also used but an additional PLC and Machine Expert are required.

See attached procedure.

Schneider Electric Česká republika

Přílohy
Disabling Password Expiration via FTP connection.pdf [81.74 KB]
Disabling Password Expiration from Machine Expert.pdf [127.31 KB]
Disabling Password Expiration using an SD card.pdf [99.79 KB]
How to use the Clone feature to restore a PLC with expired password and disable the expiration password setting.pdf [258.15 KB]
Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie