¿Cómo podemos ayudarle hoy?
Can an Altistart Soft Starter Be Powered by a Generator?
Resolution:
Yes, an Altistart soft starter can be powered by a generator; however, several factors must be considered to ensure reliable operation:
1. Non-Linear Loading
During motor starting and stopping, a soft starter creates a non-linear load. The generator must be capable of handling these operating conditions without affecting performance or stability.
2. Generator Winding Impedance
Generators typically have higher winding impedance than utility power sources. As a result, the acceleration and deceleration ramps generated by the soft starter can cause significant voltage fluctuations, which may impact other equipment connected to the same power system.
3. Generator Voltage and Frequency Stability
Soft starters rely on accurate synchronization with the incoming line voltage to properly control the SCR firing sequence. Stable voltage and frequency are critical for proper operation. The generator must be adequately sized to supply the motor's starting current demands without excessive speed, voltage, or frequency drop.
For best results, verify that the generator capacity and performance characteristics are suitable for the motor and soft starter application.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Publicado para: Schneider Electric España
Explorar más
Rango:
Explorar más
Rango:
¿Necesitas ayuda?
Selector de productos
Encuentra rápida y fácilmente los productos y accesorios adecuados para tus aplicaciones.
Pedir presupuesto
Comienza tu consulta de ventas en línea y un experto se pondrá en contacto contigo.
¿Dónde comprar?
Encuentra fácilmente el distribuidor de Schneider Electric más cercano a ti.
Centro de ayuda
Encuentra recursos de soporte para todas tus necesidades en un solo lugar.