Nuestras marcas

Web de Schneider Electric España

Bienvenido a nuestra web
		
¿Cómo podemos ayudarle hoy?
Template v.2.6.0.0.7 Missing List of Registers

Issue:

Symptoms are only present in ION Setup. When editing some Demand, Energy, or Waveform parameters, the following error message occurs:

Missing list of registers. Recommend that you edit the register list.

Error that occurs for the issue

Product Line:

ION Setup

ION8000 series

ION8300

ION8400

ION8500

Cause:

In the “FAC1 Template” setup register, V2.6.0.0.7 was misspelled as v2.6.0.0.7 by the template designer. This change in the case of ‘V” was enough to cause ION Setup to not recognize the template properly.

Resolution:

Download a new template

Workaround:

  1. Go into advanced mode of ION Setup.
  2. Go to the Factory Module.
  3. Find “FAC1 Template” on the setup registers tab.
  4. Click Edit
  5. Change the small 'v' to an uppercase 'V'
  6. Select OK to save change

Image of Changed V for FAC1 Template

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies