Nuestras marcas

Impact-Company-Logo-English Black-01-177x54

Web de Schneider Electric España

Bienvenido a nuestra web
		
¿Cómo podemos ayudarle hoy?
MODNET string variable configuration

Summary:

I have configured a string variable communicating to a PLC via MODNET and I can only see the first 2 characters of the string. How can I see the whole string?

Solution:

If you specify a string tag with the address 40001, the MODNET driver will only read register 40001 (2 bytes so 2 characters). If you want a string longer than 2 characters you have to create your tag as an array of characters so the driver knows how long the string is. So if you want a string of length 10 you need to setup an array of length 5. image


Keywords:

MODBUS

________________________________________

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies