Nuestras marcas

Impact-Company-Logo-English Black-01-177x54

Web de Schneider Electric España

Bienvenido a nuestra web
		
¿Cómo podemos ayudarle hoy?
How to perform a soft reset on a CM3000/4000 and PM800 series

Issue
Unable to power cycle the meter physically.

Product Line
CM3000/4000

PM800 series

Environment

PM800 Series and CM3000/4000 Series

Modbus Tester or other Register Writing Applications

Causes
Sometimes local access to where the meters are installed isn't possible or access to the wiring of the meter is blocked.

Resolution

Can remotely perform a soft reset of these devices by writing a specific register value to the setup register.

Will require an application or tool like Modbus Tester or some other software that allows the user to write to the registers of the devices.

  1. Write 9020 to register 8000 to put the device in setup mode.
  2. Write 1110 to register 8000. This will reset the meter.

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies