Does There Exist a USB to RS-232 Converter for SFT2841 Software and Sepam Front Port Connection

Issue

User needs to know if a USB to RS-232 converter can be used with SFT2841 software and the Sepam mini-DIN front port connection.

Product

SFT2841 Software
Sepam Protection Relays

Environment

PC communication setup with Sepam relays via mini-DIN front port

Cause

Modern computers often lack RS-232 serial ports, requiring the use of USB to RS-232 converters. However, compatibility issues may arise depending on the converter drivers and COM port configuration used by SFT2841.

Resolution

It is recommended to use the Telemecanique TSXCUSB232 USB to RS-232 converter, as it uses drivers already supported and installed by the SFT2841 software.

Additional considerations:

  • For SFT2841 versions up to V10.1:
    • Only COM ports 1 to 4 should be used for Sepam 40 communication
    • Although COM ports 1 to 9 may appear available, using ports above COM4 can result in user messages and logical equations not being properly loaded
  • For SFT2841 version 10.3 and later (released Q4 2008):
    • All COM ports supported by the operating system can be used without restriction

Using the recommended converter ensures reliable communication between the PC and Sepam relay via the front port.

Schneider Electric España

Explorar más
Producto:
Rango:
Explorar más
Producto:
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Condiciones generales de contratación
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies
  • Centro de Preferencias