¿Cómo podemos ayudarle hoy?

What is the difference between Retain and Persistent variables in SoMachine V4.3?

Issue:

What is the difference between Retain and Persistent variables in SoMachine V4.3?

Product Line:

SoMachine V4.3

Resolution:

1: Retain variables will be reinitialized after: reset cold, reset origin and application download otherwise the values are maintained;

2: Persistent variables will be reinitialized after Reset origin only;

Note: Persistent and Persistent Retain are the same (different wording comes from prior versions of CoDeSys);

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Condiciones generales de contratación
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies
  • Centro de Preferencias