Nuestras marcas

Impact-Company-Logo-English Black-01-177x54

Web de Schneider Electric España

Bienvenido a nuestra web
		
¿Cómo podemos ayudarle hoy?
What are some possible causes for the torque control not to work on an ATV71?

Article available in these languages: Español

Issue:
Torque control not working

Product Line:
ATV71

Environment:
All models and serial numbers

Cause:
Motor control type not set to SVCI
torque/speed not enabled [Trq/spd switching]
Torque reference channel not assigned [Torque ref. channel]
Speed reference not assigned

Resolution:
Set motor control type t SVCI
Enable torque speed switching.  Set to "Yes" for permanent torque control or assign a logic input.
Assign a torque reference channel.  This can be set as the low speed, preset speed, analog input, serial comm or encoder feedback.
Assign a speed reference (do not assign it to the same as torque reference channel)

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:

¿Necesitas ayuda?

  • Selector de productos

    Encuentra rápida y fácilmente los productos y accesorios adecuados para tus aplicaciones.

  • Pedir presupuesto

    Comienza tu consulta de ventas en línea y un experto se pondrá en contacto contigo.

  • ¿Dónde comprar?

    Encuentra fácilmente el distribuidor de Schneider Electric más cercano a ti.

  • Centro de ayuda

    Encuentra recursos de soporte para todas tus necesidades en un solo lugar.

  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies