Modifying the Default Database Path and the SQL Errorlog Path

Issue
If databases, particularly the system databases, have been relocated to a new drive/volume or the disk configuration has changed,
a recommended best practice would be to change the SQL Server Agent log path as well as the Default Database locations path.

Product
Power Monitoring Expert 7.2.x

Power Monitoring Expert 8.x

Power Monitoring Expert 9.x

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment
SQL Server Instance

Cause
The SQL Agent may fail to start, or creating a database may fail if the original drive letter\path does not exist anymore.

Resolution
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*


To change the SQL Agent log path:
1. In SQL Server Management Studio expand SQL Server Agent
2. Right-click on Errorlogs
3. Click on Configure
4. Change the Error Log File path to the new desired location

To change the Database Default Locations path
1. In SQL Server Management Studio right-click on the SQL Server name
2. Choose Prooperties
3. Choose Database Settings
4. Under "Database Default Locations" modify the Data and Log paths to the new, desired location

Schneider Electric España

Explorar más
Producto:
Explorar más
Producto:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies