Nuestras marcas

Web de Schneider Electric España

Bienvenido a nuestra web
		
¿Cómo podemos ayudarle hoy?
What can cause an OC3 fault on the ATV21 and ATV212 drives?
Issue:
Why does OC3 trips on the ATV21/ATV212 drives?

Product Line:
Altivar ATV21 ATV212 S-Flex

Environment:
All models

Cause:
The drive is running and intermittently trips on the OC3 fault.

Resolution:
OC3 means overcurrent during constant speed operation.

Possible causes:
Abrupt fluctuations in the load or abnormal load conditions.

Remedies:
Reduce the load fluctuations
Check your load
Set parameter F316 to 1 or 3

OC3 can be cleared by Auto Restart as long as the condition that causes the fault is resolved.
To turn on Auto Restart set F303 to any value between 1 and 10. This value is the number attempts to clear the fault.

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies