Nuestras marcas

Web de Schneider Electric España

Bienvenido a nuestra web
		
¿Cómo podemos ayudarle hoy?
Does Control Expert (formerly Unity Pro) offer a way to detect if an ERIO drop has a problem on one or more of its IO modules?

Issue:

Does Control Expert (formerly Unity Pro) offer a way to detect if an ERIO drop has a problem on one or more of its IO modules?

Product Line:

Control Expert, Unity Pro, ERIO drop

Resolution:

Yes, the following System Words can be used to determine module health in an ERIO drop.

%SW152-153  Referred to as ERIO_Drop_Status
0=There is a problem with one or more modules in this drop
1=Drop status is good, no IO problems in this drop


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies