Can we have different DNP sever sessions to talk with different SCADA clients

Question:
Can we have different DNP sever sessions to talk with different SCADA clients. Cause customer has two SCADA clients & they have respective master/slave address.


Answer:
No.
DNP3 as TCP server only supports one session with one set of master/slave address.
So customer has to adjust the two clients as same master/slave address to talk with the common session in NOR.
If they would like two customized sessions at NOR part, two NOR modules are needed.