¿Cómo podemos ayudarle hoy?

EBO SNVT types of third party devices doesnt match with SNVT types in TAC Vsta

EBO system processes data from third-party LonWorks devices according to the definition by Device Template, which is imported to a Building Operation Server (ES/AS-P).

In case SNVT types visible in EBO don't match with SNVTs in the TAC Vista database after the conversion procedure is done, there must be a discrepancy in XIF files that have been imported in advance.

Check the Network Variable index numbers for particular SNVTs that do not match after conversion against XIF files.

Make XIF file correction manually, following the LonMark org Technical Resource guide
chrome-extension://efaidnbmnnnibpcajpcglclefindmkaj/https://www.lonmark.org/wp-content/uploads/2020/12/LmXif4501.pdf

Schneider Electric España

Explorar más
Producto:
Explorar más
Producto:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies