¿Cómo podemos ayudarle hoy?

How to Update the Application for the Vigilohm IMDLRDH

Note: Implementing a new application in your IMDLRDH will erase your previous configuration.

To update the application program of your IMDLRDH you need to:

Have a formatted USB Pen Drive in FAT32 format.

Unzip the content of application zip file and place the extracted files on the root of your USB Key.

Image showing the extracted application file in root of the USB Drive

Switch off the IMDLRDH

Plug the USB Key in the USB port of the IMDLRDH

Image showing USB port of IMLRDH where the USB Drive needs to be inserted

Power on the IMDLRDH, wait until the installation confirmation screen appears.

Image showing the confirmation to install the application file

Press Yes to Start the installation.

Device will restart and installation will start automatically.

Image showing the installation progress

Wait for the program to be installed completely in the IMDLRDH

Once installation is complete this screen will appear.

Image showing the installation is complete

Remove the USB Pen Drive and click restart.

After these steps you need to perform the commissioning of your IMDLRDH.

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Condiciones generales de contratación
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies
  • Centro de Preferencias