What is the MODBUS Register Mapping of SNTP Diagnostics Data for CPUs and communication modules in M580?

SNTP Diagnostic data of 57 words, are available on CPUs and BMENOC0301/11 communication modules using Modbus function code 3 with the unit ID set to 100, offset Modbus Address 1218 and below is the MODBUS Register Mapping:

AddressMS ByteLS ByteCIP TypeComments
1218MSW - MSBMSW - LSBUint32Primary NTP Server IP Address
Offset + 01LSW - MSBLSW - LSB
Offset + 02MSW - MSBMSW - LSBUint32Secondary NTP Server IP Address
Offset + 03LSW - MSBLSW - LSB
Offset + 04UnusedBYTEUint8Polling Period (in seconds)
Offset + 05UnusedBYTEUint8Update CPU with Module Time
Offset + 06MSW - MSBMSW - LSBUint32Time Zone
Offset + 07LSW - MSBLSW - LSB
Offset + 08MSBLSBInt16Time Zone Offset (in minutes)
Offset + 09UnusedBYTEUint8Daylight saving time bias (in minutes)
Offset + 10UnusedLSBUint8Daylight Saving Start Date - Month
Offset + 11UnusedLSBUint8Daylight Saving Start Date - week #, day of week
MS 4-bits: occurrence # (1 = 1st occurrence, 2 = 2nd occurrence…, 5 = fifth or last occurrence)
LS 4-bits: day of the week (0 = Sunday…, 6 = Saturday)
Offset + 12MSW - MSBMSW - LSBUint32Daylight Saving Start Time (seconds elapsed from midnight)
Offset + 13LSW - MSBLSW - LSB
Offset + 14UnusedLSBUint8Daylight Saving End Date - Month
Offset + 15UnusedLSBUint8Daylight Saving End Date - week #, day of week
Offset + 16MSW - MSBMSW - LSBUint32Daylight Saving End Time (seconds elapsed from midnight)
Offset + 17LSW - MSBLSW - LSB
Offset + 18UnusedBYTEUint8SNTP Mode
Offset + 19UnusedBYTEUint8Reserved
…
Offset + 32UnusedBYTEUint8Reserved
Offset + 33MSW - MSBMSW - LSBUDINTNetwork Time Service Status
Offset + 34LSW - MSBLSW - LSB
Offset + 35MSW - MSBMSW - LSBUDINTLink to NTP Server Status
Offset + 36LSW - MSBLSW - LSB
Offset + 37MSW - MSBMSW - LSBUDINTCurrent NTP Server IP Address
Offset + 38LSW - MSBLSW - LSB
Offset + 39MSW - MSBMSW - LSBUDINTNTP NTP Server Type
Offset + 40LSW - MSBLSW - LSB
Offset + 41MSW - MSBMSW - LSBUDINTNTP Server Time Quality
Offset + 42LSW - MSBLSW - LSB
Offset + 43MSW - MSBMSW - LSBUDINTNumber of NTP Requests Sent
Offset + 44LSW - MSBLSW - LSB
Offset + 45MSW - MSBMSW - LSBUDINTNumber of Communication Errors
Offset + 46LSW - MSBLSW - LSB
Offset + 47MSW - MSBMSW - LSBUDINTNumber of NTP Reponses Received
Offset + 48LSW - MSBLSW - LSB
Offset + 49MSBLSBUINTLast Error
Offset + 50MSW - MSBMSW - LSBUDINTCurrent Time
Offset + 51LSW - MSBLSW - LSB
Offset + 52MSBLSBUINTCurrent Date
Offset + 53MSW - MSBMSW - LSBUDINTDaylight Savings Status
Offset + 54LSW - MSBLSW - LSB
Offset + 55MSW - MSBMSW - LSBDINTTime Since Last Update
Offset + 56LSW - MSBLSW - LSB

Schneider Electric España

Explorar más

Explorar más

¿Necesitas ayuda?

Selector de productos

Encuentra rápida y fácilmente los productos y accesorios adecuados para tus aplicaciones.

Pedir presupuesto

Comienza tu consulta de ventas en línea y un experto se pondrá en contacto contigo.

¿Dónde comprar?

Encuentra fácilmente el distribuidor de Schneider Electric más cercano a ti.

Centro de ayuda

Encuentra recursos de soporte para todas tus necesidades en un solo lugar.