¿Cómo podemos ayudarle hoy?

Ecostruxure Process Expert [2020R2]:How to use "Exec" Function in supervision participant of EPE

This document explains the parameters or settings to be set in Supervision participant to enable the "EXEC" function.

Citect Scada 2018 Supervision participant in Ecostruxure Process Expert 2020 introduced Additional security features, now requires user permission to call the Exec() function.

The user needs to perform the following steps to enable to "EXEC" Function.

1. Open refinement of Supervision Project and Set the Allow Exec field to TRUE for permitted users under Roles in Security.

pic1

2. Add the following parameter in the Citect.ini file

[Security]

BlockExec = 0


This document is applicable for Ecostruxure Process Expert 2020R1 & Ecostruxure Process Expert 2020R2.

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies