Nuestras marcas

Web de Schneider Electric España

Bienvenido a nuestra web
		
¿Cómo podemos ayudarle hoy?
When can we use a DC Injection braking on Altivar Process drives (Type of stop)?

Issue:
The drive is not stopping even without a run command, deceleration ramp up time has been already finished.
DI1 not energized, no delays assigned on DI1 for a start or stop.
Whenever the contactor for the DI1 and the 24V is open, the drive will start decreasing the speed, but it never goes to 0.0hz.

Resolution:
DC injection braking provides a quick and smooth braking action on all types of loads, including high-speed and high-inertia loads.
In an AC induction motor, when the AC voltage is removed, the motor will coast to a standstill over a period of time, since there is no induced field to keep it rotating. Since the coasting time may be unacceptable, particularly in an emergency situation, electric braking can be used to provide a more immediate stop.

Go to [Complete Settings] --> [Generic Functions] --> [Stop Configuration]
look for [Type of Stop] Stt
Select DC injection (This will be only available if motor control type is not set to [SYN_U CV] or [Rel.Mot])

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric España

Documentos adjuntos
DC bus injection.jfif [84.16 KB]
Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies