¿Cómo podemos ayudarle hoy?

How to save multiple variable values in Event Logging to a Single CSV File?

Issue:

Want to save data to USB drive on HMIGTO3410 by following the instruction "Save Variable to a Single CSV File, section 13.1.1.5 in the manual"

Product Line:

Vijeo Designer (all versions)

Resolution:

The following video on How to log data using Event Handling in Vijeo Designer, shows how it can be done:

https://www.youtube.com/watch?v=AvucNI5wELE

In it, they indicate to use 2 Text Resources in order to write the data on 2 lines in the file.

But, in Vijeo Designer, it is possible to use only 1 Text Resources and configure 2 (or more) messages:

Text ressource

Then when configuring the Action that will generate the messages, use only 1 Text Resource but use the 2 messages in the actions instead of 2 Text Resources and only 1 message in each.

Actions configuration

This way would be better suited for the management of messages and what they are used for in the project.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Condiciones generales de contratación
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies
  • Centro de Preferencias